Canon PSC 2000 User Manual

Browse online or download User Manual for Air blowers/dryers Canon PSC 2000. Canon PSC 2000 User's Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 58
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
2000 Fire Door-Fan Manual updated 2002-05-28 Page 1 of 58
2000 Fire Door-Fan Manual
Single Blower Panel Set
Up
with Model N digital
console
OR, Model L digital
control panel
OR, Model E analog
gauge clip
Large room testing with
2 Blowers
Or, E43 Aluminum
Frame Set Up
Leak check at + 15Pa
Room pressure
Smoke test &
measure static pressure
Range Selection
Room and Flow
Pressure Readings
Windy test conditions
Mixing or NO mixing?
Page view 0
1 2 3 4 5 6 ... 57 58

Summary of Contents

Page 1 - 2000 Fire Door-Fan Manual

2000 Fire Door-Fan Manual updated 2002-05-28 Page 1 of 58 2000 Fire Door-Fan Manual Single Blower Panel Set Up with Model N digi

Page 2 - Page 2 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 10 of 58 OR, DM-1 digital gauge for models J64 OR, DM-1 digital gauge The digi

Page 3 - Single Blower Panel Set Up

2000 Fire Door-Fan Manual updated 2002-05-28 Page 11 of 58 Take the 7ft red tube and throw outside, away from the air blast o

Page 4 - Page 4 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 12 of 58 Install the X-Y Panel. Expand the X-Y panel horizontally by hand.

Page 5 - Page 5 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 13 of 58 Red tube is always extended away from the air-stream on the opposite

Page 6

2000 Fire Door-Fan Manual updated 2002-05-28 Page 14 of 58 This detailed picture shows white dots that should line up. Later m

Page 7

2000 Fire Door-Fan Manual updated 2002-05-28 Page 15 of 58 Large room testing with 2 Blowers Models N64 and L64 Use the second

Page 8

2000 Fire Door-Fan Manual updated 2002-05-28 Page 16 of 58 Or, E43 Aluminum Frame Set Up Open case Take out pieces Assemb

Page 9

2000 Fire Door-Fan Manual updated 2002-05-28 Page 17 of 58 Actuate cam levers Frame is installed. Hook elastic under blower.

Page 10 - Page 10 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 18 of 58 Leak Check The Purpose of the leak check is to locate the major leaks

Page 11 - Page 11 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 19 of 58 Smoke test & measure static pressure The purpose of this test i

Page 12 - Page 12 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 2 of 58 What to do if room fails. Lower leak tests using: Flex-duct ceili

Page 13 - Page 13 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 20 of 58 Select Blower Range Principles of Infiltrometer Air Flow Measurement

Page 14 - Page 14 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 21 of 58 Range Selection Procedure Always start with the restrictor plate off

Page 15 - Page 15 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 22 of 58 Flow Range Diagram Always start in the Flow Away position. Adjust spe

Page 16 - Page 16 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 23 of 58 Range C1 - Flow Away Range 22 - Flow Towards Range A - Flow To

Page 17 - Page 17 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 24 of 58 Room and Flow Pressure Readings Make sure the blower is running at ha

Page 18 - Leak Check

2000 Fire Door-Fan Manual updated 2002-05-28 Page 25 of 58 60 gauge readings Read the upper scale only. Reverse the tubes when

Page 19

2000 Fire Door-Fan Manual updated 2002-05-28 Page 26 of 58 Digital Gauge Readings Model DM-1 Digital Gauge for models N64

Page 20 - Select Blower Range

2000 Fire Door-Fan Manual updated 2002-05-28 Page 27 of 58 1.Turn ON the DM-1. Wait 30 seconds. Set first toggle to “ZERO” 2. P

Page 21 - Range Selection Procedure

2000 Fire Door-Fan Manual updated 2002-05-28 Page 28 of 58 Two blowers for large rooms, (see also section on flex-duct testing)

Page 22 - Page 22 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 29 of 58 Windy Conditions If the gauges fluctuate more than 1 Pa due to wind,

Page 23 - Page 23 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 3 of 58 Single Blower Panel Set Up Select a doorway where the air will be b

Page 24 - 5 Pa division

2000 Fire Door-Fan Manual updated 2002-05-28 Page 30 of 58 Use averaging on digital gauge to reduce the effect of wind. Set t

Page 25

2000 Fire Door-Fan Manual updated 2002-05-28 Page 31 of 58 Deluxe Wind Damping System to Stop Gauge Needles Moving If the room p

Page 26 - Digital Gauge Readings

2000 Fire Door-Fan Manual updated 2002-05-28 Page 32 of 58 Mixing or No Mixing (Descending Interface) or Extended Discharge

Page 27 - Page 27 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 33 of 58 If the room fails Equipment calibration is often blamed for these fa

Page 28 - Page 28 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 34 of 58 This will only help if there is continual mixing during the retention

Page 29 - Windy Conditions

2000 Fire Door-Fan Manual updated 2002-05-28 Page 35 of 58 Flex duct installation for ceiling neutralization Position the fle

Page 30

2000 Fire Door-Fan Manual updated 2002-05-28 Page 36 of 58 A ceiling tile is removed to allow the flex duct to be mounted Note

Page 31

2000 Fire Door-Fan Manual updated 2002-05-28 Page 37 of 58 Lower leak tests using: Plastic-on-Ceiling procedure This procedure i

Page 32

2000 Fire Door-Fan Manual updated 2002-05-28 Page 38 of 58 The principal deviation from the normal procedure is that the test can

Page 33 - If the room fails

2000 Fire Door-Fan Manual updated 2002-05-28 Page 39 of 58 Lower leak Estimates using: Leak audit Set the door fan to produce a

Page 34

2000 Fire Door-Fan Manual updated 2002-05-28 Page 4 of 58 Cinch lower strap tight and secure strap in cleat. The small fill-

Page 35 - Page 35 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 40 of 58 Field calibration check with calibration plate Place the second Blo

Page 36

2000 Fire Door-Fan Manual updated 2002-05-28 Page 41 of 58 The Field Calibration Check is a procedure which enables the AHJ to de

Page 37

2000 Fire Door-Fan Manual updated 2002-05-28 Page 42 of 58 Tall doorways Small X panel being installed. X- Panel will add 10

Page 38

2000 Fire Door-Fan Manual updated 2002-05-28 Page 43 of 58 Packing up and moving equipment Blower case fits on Ruaax cart.

Page 39

2000 Fire Door-Fan Manual updated 2002-05-28 Page 44 of 58 Case protects blower for day to day transport but when shipped by s

Page 40 - Page 40 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 45 of 58 Large building Testing Retrotec’s multiple fan panels can be added i

Page 41

2000 Fire Door-Fan Manual updated 2002-05-28 Page 46 of 58 Recalibration of Retrotec Infiltrometer The NFPA Appendix C requires

Page 42 - Tall doorways

2000 Fire Door-Fan Manual updated 2002-05-28 Page 47 of 58 Retrotec Gauge and System Calibration All Retrotec Gauges are calibra

Page 43 - Page 43 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 48 of 58 For a complete calibration, take the gauge up to full scale, hold it t

Page 44 - Page 44 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 49 of 58 Retrotec gauge calibration software was developed especially for mee

Page 45 - Large building Testing

2000 Fire Door-Fan Manual updated 2002-05-28 Page 5 of 58 Hook the bottom foot on the blower through the hole in the center o

Page 46 - Page 46 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 50 of 58 Troubleshooting, Maintenance, Repair The printer tried to print but c

Page 47

2000 Fire Door-Fan Manual updated 2002-05-28 Page 51 of 58 • Make sure that the paper is loaded and turn the power switch ON. •

Page 48

2000 Fire Door-Fan Manual updated 2002-05-28 Page 52 of 58 BJ30 Print Head Cleaning The print head contains nozzles through whi

Page 49 - Page 49 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 53 of 58 Balancing Indoor/Outdoor Temperature Readings The control

Page 50 - Page 50 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 54 of 58 Figure 3 Out lined in red are the two places that will need to have

Page 51 - Page 51 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 55 of 58 Possible Mechanical Problems Panels Will Not Fit Doorway Try using

Page 52 - BJ30 Print Head Cleaning

2000 Fire Door-Fan Manual updated 2002-05-28 Page 56 of 58 for leaks in the gauges by blowing in the tube, then folding the tube

Page 53 - Page 53 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 57 of 58 Thermometer Replacement If the thermometer does not read correctly a

Page 54 - Page 54 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 58 of 58 The Retrotec Infiltrometer is warranted for two years parts and labor,

Page 55 - Page 55 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 6 of 58 Set up Model N digital console Place Laptop Console on blower case.

Page 56 - Page 56 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 7 of 58 Your laptop computer power supply plugs into the female plug inside t

Page 57 - Page 57 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 8 of 58 OR, Model L digital control panel for Models L64 and L63 The control

Page 58 - Page 58 of 58

2000 Fire Door-Fan Manual updated 2002-05-28 Page 9 of 58 OR, Model E analog gauge clip for models E43, E53, E54 The Gauge

Comments to this Manuals

No comments